Technische illustratie. Representative component image; exact configuration and appearance may vary. Afbeeldingen zijn uitsluitend ter referentie. Het geleverde onderdeel kan er anders uitzien.
1SAE351111R0631 — Installation Contactor
contactorOnderdeelnummer: 1SAE351111R0631
ABB ESB63-31N-06 (1SAE351111R0631) is a four-pole installation contactor with three normally open and one normally closed main contact. It has a 230 V rated control circuit and a normally open AC-1 current rating of 63 A. The contactor occupies three modular spacings and measures 54 × 85 × 65 mm (width × height × depth). Select according to the circuit voltage, load and duty.
Op zoek naar ABB 1SAE351111R0631? Deze catalogusreferentie is ingedeeld als ‘contactor’. Stuur het onderdeelnummer en de gegevens van uw machine, zodat we de specificaties en beschikbaarheid kunnen controleren en een offerte inclusief verzending kunnen opstellen.
Beschikbaarheid op aanvraag
Technische specificaties
| Fabrikant | ABB |
|---|---|
| Onderdeelnummer | 1SAE351111R0631 |
| Categorie | Elektrotechniek en besturing |
| Product Net Width | 54 mm |
| Product Net Depth / Length | 65 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 0.405 kg |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Rated Operational Voltage | Main circuit: 400 V AC; 220 V DC |
| Rated Frequency (f) | Control circuit: 50 Hz, 60 Hz, 400 Hz and DC; main circuit: 50 Hz, 60 Hz and DC |
| Rated Operational Current AC-1 (I e ) | Normally open: 63 A; normally closed: 30 A |
| Rated Operational Current AC-3 (I e ) | Normally open: 30 A at 230 V single-phase or 400 V three-phase |
| Rated Operational Current AC-7a (I e ) | (NO) 63 A |
| Rated Operational Current AC-7b (I e ) | (230 V) Single Phase, NO 30 A |
| Rated Operational Power AC-1 (P e ) | (230 V) Single Phase, NC 6.9 kW |
| Rated Operational Power AC-3 (P e ) | Normally open: 5 kW at 230 V single-phase; 15 kW at 400 V three-phase |
| Rated Operational Power AC-7a (P e ) | (230 V) Single Phase, NC 6.9 kW |
| Rated Operational Power AC-7b (P e ) | (230 V) Single Phase, NO 5 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (I cw ) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 240 A |
| Rated Insulation Voltage (U i ) | 500 V |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (U c ) | 230 V |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 4.5 W |
| Published component type | Installation Contactor |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Ambient Air Temperature | Operation: -25 to +55 °C; storage: -40 to +80 °C |
| Width in Modular Spacings | 3 |
Catalogusinformatie kan fouten bevatten of verouderd zijn. Volledige specificaties en gecontroleerde gegevens zijn op aanvraag beschikbaar. Bevestig vóór bestelling het onderdeelnummer en de geschiktheid voor uw machine met ons.
Productvragen
Onderzoeksinformatie over dit onderdeel is nog niet beschikbaar in het Nederlands. Vraag ons team om hulp.
Offerte voor dit onderdeel aanvragen