ABB MS116-0.4 (1SAM250000R1003) is a three-pole manual motor starter with an adjustable 0.25–0.40 A overload setting. It provides overload and short-circuit protection, phase-loss sensitivity and manual motor switching. Its rated AC-3 operational power is 0.09 kW at 400 V.

Op zoek naar ABB 1SAM250000R1003? Deze catalogusreferentie is ingedeeld als ‘Elektrotechniek en besturing’. Stuur het onderdeelnummer en de gegevens van uw machine, zodat we de specificaties en beschikbaarheid kunnen controleren en een offerte inclusief verzending kunnen opstellen.

Beschikbaarheid op aanvraag

Prijs op aanvraag

Verzending inbegrepenGarantie en serviceOfferte voor dit onderdeel aanvragen

Technische specificaties

FabrikantABB
Onderdeelnummer1SAM250000R1003
CategorieElektrotechniek en besturing
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter MS116-0.40 valid for productiondate from week 34/2014
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS116
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length85.6 mm
Product Net Weight0.225 kg
Rated Service Short-Circuit Breaking Capacity (I cs )50 kA at 230 V AC; 50 kA at 400 V AC
Rated Ultimate Short-Circuit Breaking Capacity (I cu )100 kA at 230 V AC; 100 kA at 400 V AC
Rated Instantaneous Short-Circuit Current Setting (I i )5 A
Setting Range0.25–0.40 A
Rated Operational Power AC-3 (P e )0.09 kW at 400 V
Rated Operational Power AC-3e (P e )(400 V) Three Phase 0.09 kW
Rated Operational Voltage690 V AC, main circuit
Rated Operational Current (I e )0.4 A
Rated Operational Current AC-3 (I e )0.4 A
Rated Operational Current AC-3e (I e )0.4 A
Rated Frequency (f)50/60 Hz, main circuit
Rated Impulse Withstand Voltage (U imp )6 kV, main circuit
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 0.6 ... 1.7 W
Number of Poles3
Conventional Free-air Thermal Current (I th )Main Circuit 0.4 A
Degree of ProtectionHousing IP20; main circuit terminals IP10
Terminal TypeScrew terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Mounting Position1 ... 6
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Trip Class10A
Mounting35 mm DIN rail TH35-7.5 or TH35-15

Catalogusinformatie kan fouten bevatten of verouderd zijn. Volledige specificaties en gecontroleerde gegevens zijn op aanvraag beschikbaar. Bevestig vóór bestelling het onderdeelnummer en de geschiktheid voor uw machine met ons.