Technische illustratie. Representative component image; exact configuration and appearance may vary. Afbeeldingen zijn uitsluitend ter referentie. Het geleverde onderdeel kan er anders uitzien.
1SAM250000R1005 — Motor protection circuit-breaker
Elektrotechniek en besturingOnderdeelnummer: 1SAM250000R1005
ABB MS116-1.0 (1SAM250000R1005) is a three-pole motor protection circuit-breaker with screw terminals and an adjustable overload setting of 0.63–1.0 A. It has a rated operational current of 1 A, thermal overload and short-circuit protection, and phase-failure sensitivity. At 400 V AC its rated service short-circuit breaking capacity is 50 kA.
Op zoek naar ABB 1SAM250000R1005? Deze catalogusreferentie is ingedeeld als ‘Elektrotechniek en besturing’. Stuur het onderdeelnummer en de gegevens van uw machine, zodat we de specificaties en beschikbaarheid kunnen controleren en een offerte inclusief verzending kunnen opstellen.
Beschikbaarheid op aanvraag
Technische specificaties
| Fabrikant | ABB |
|---|---|
| Onderdeelnummer | 1SAM250000R1005 |
| Categorie | Elektrotechniek en besturing |
| Time-Current Characteristic Curve | Tripping characteristic - Manual Motor Starter MS116-1.0 valid for production date from week 34/2014 |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400V -Manual Motor Starter MS116 |
| Product Net Width | 45 mm |
| Product Net Height | 90 mm |
| Product Net Depth / Length | 85.6 mm |
| Product Net Weight | 0.225 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | 50 kA at 230 V AC; 50 kA at 400 V AC; 50 kA at 440 V AC; 30 kA at 500 V AC; 30 kA at 690 V AC |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | 100 kA at 230, 400, 440, 500 and 690 V AC |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 12.5 A |
| Setting Range | 0.63–1.0 A |
| Rated Operational Power AC-3 (P e ) | 0.25 kW at 400 V, three-phase |
| Rated Operational Power AC-3e (P e ) | (400 V) Three Phase 0.25 kW |
| Rated Operational Voltage | Main circuit: 690 V AC |
| Rated Operational Current (I e ) | 1 A |
| Rated Operational Current AC-3 (I e ) | 1 A |
| Rated Operational Current AC-3e (I e ) | 1 A |
| Rated Frequency (f) | Main circuit: 50/60 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Main Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 0.6 ... 1.6 W |
| Number of Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 1 A |
| Degree of Protection | Housing IP20; main circuit terminals IP10 |
| Terminal Type | Screw terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Tightening Torque | Main Circuit 0.8 ... 1.2 N·m |
| Wire Stripping Length | Main Circuit 9 mm |
| Mounting Position | 1 ... 6 |
| Published component type | Motor protection circuit-breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Integrated Auxiliary Switch | No |
Catalogusinformatie kan fouten bevatten of verouderd zijn. Volledige specificaties en gecontroleerde gegevens zijn op aanvraag beschikbaar. Bevestig vóór bestelling het onderdeelnummer en de geschiktheid voor uw machine met ons.
Productvragen
Onderzoeksinformatie over dit onderdeel is nog niet beschikbaar in het Nederlands. Vraag ons team om hulp.
Offerte voor dit onderdeel aanvragen