Technische illustratie. Representative component image; exact configuration and appearance may vary. Afbeeldingen zijn uitsluitend ter referentie. Het geleverde onderdeel kan er anders uitzien.
1SAM250000R1013 — Motor protection circuit-breaker
Elektrotechniek en besturingOnderdeelnummer: 1SAM250000R1013
ABB MS116-20, part number 1SAM250000R1013, is a three-pole manual motor starter with an adjustable 16–20 A overload setting. It provides overload, short-circuit and phase-loss protection, with a rotary manual control and trip class 10A. The device is suitable for single-phase and three-phase applications, subject to correct selection and connection.
Op zoek naar ABB 1SAM250000R1013? Deze catalogusreferentie is ingedeeld als ‘Elektrotechniek en besturing’. Stuur het onderdeelnummer en de gegevens van uw machine, zodat we de specificaties en beschikbaarheid kunnen controleren en een offerte inclusief verzending kunnen opstellen.
Beschikbaarheid op aanvraag
Technische specificaties
| Fabrikant | ABB |
|---|---|
| Onderdeelnummer | 1SAM250000R1013 |
| Categorie | Elektrotechniek en besturing |
| Time-Current Characteristic Curve | Tripping characteristic - Manual Motor Starter MS116-20 |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400V -Manual Motor Starter MS116 |
| Product Net Width | 45 mm |
| Product Net Height | 97.8 mm |
| Product Net Depth / Length | 85.4 mm |
| Product Net Weight | 0.31 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | 10 kA at 230 V AC and 400 V AC |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | 16 kA at 230 V AC and 400 V AC |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 300 A |
| Setting Range | 16–20 A |
| Rated Operational Power AC-3 (P e ) | 7.5 kW at 400 V, three-phase |
| Rated Operational Power AC-3e (P e ) | (400 V) Three Phase 7.5 kW |
| Rated Operational Voltage | Main circuit: 690 V AC |
| Rated Operational Current (I e ) | 20 A |
| Rated Operational Current AC-3 (I e ) | 20 A |
| Rated Operational Current AC-3e (I e ) | 20 A |
| Rated Frequency (f) | Main circuit: 50/60 Hz |
| Rated Impulse Withstand Voltage (U imp ) | 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 1.5 ... 2.3 W |
| Number of Poles | 3 |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 20 A |
| Degree of Protection | Housing IP20 |
| Terminal Type | Screw Terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 6 mm² |
| Tightening Torque | Main Circuit 2 N·m |
| Wire Stripping Length | Main Circuit 10 mm |
| Mounting Position | 1 ... 6 |
| Published component type | Motor protection circuit-breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Trip class | 10A |
Catalogusinformatie kan fouten bevatten of verouderd zijn. Volledige specificaties en gecontroleerde gegevens zijn op aanvraag beschikbaar. Bevestig vóór bestelling het onderdeelnummer en de geschiktheid voor uw machine met ons.
Productvragen
Onderzoeksinformatie over dit onderdeel is nog niet beschikbaar in het Nederlands. Vraag ons team om hulp.
Offerte voor dit onderdeel aanvragen