Technische illustratie — ABB 1SAM340000R1003 — 1SAM340000R1003 — Power circuit-breaker for trafo/generator/installation protection

Technische illustratie. Representative component image; exact configuration and appearance may vary. Afbeeldingen zijn uitsluitend ter referentie. Het geleverde onderdeel kan er anders uitzien.

ABB

1SAM340000R1003 — Power circuit-breaker for trafo/generator/installation protection

Elektrotechniek en besturing

Onderdeelnummer: 1SAM340000R1003

ABB 1SAM340000R1003 (MS132-0.4T) is a three-pole circuit breaker designed for primary-side protection of control transformers against overload and short circuit. It has a 0.25–0.40 A adjustable current range, screw terminals and a lockable rotary handle. Its rated service breaking capacity is 100 kA at 400 V AC. Confirm suitability for the transformer and installation before selection.

Op zoek naar ABB 1SAM340000R1003? Deze catalogusreferentie is ingedeeld als ‘Elektrotechniek en besturing’. Stuur het onderdeelnummer en de gegevens van uw machine, zodat we de specificaties en beschikbaarheid kunnen controleren en een offerte inclusief verzending kunnen opstellen.

Beschikbaarheid op aanvraag

Prijs op aanvraag

Verzending inbegrepenGarantie en serviceOfferte voor dit onderdeel aanvragen

Technische specificaties

FabrikantABB
Onderdeelnummer1SAM340000R1003
CategorieElektrotechniek en besturing
Time-Current Characteristic CurveTripping characteristic - Circuit Breaker for Transformer Protection MS132-0.4T
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V - Circuit Breaker for Transformer Protection MS132-T / MS132-KT
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length86.75 mm
Product Net Weight0.215 kg
Rated Service Short-Circuit Breaking Capacity (I cs )100 kA at 230 V AC; 100 kA at 400 V AC
Rated Ultimate Short-Circuit Breaking Capacity (I cu )(400 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (I i )8 A
Setting Range0.25 ... 0.40 A
Rated Operational VoltageMain Circuit 690 V AC
Rated Operational Current (I e )0.4 A
Rated Frequency (f)Main circuit 50/60 Hz
Operating Frequency (f sw )0 ... 400 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 0.6 ... 1.5 W
Number of Poles3P
Conventional Free-air Thermal Current (I th )Main Circuit 0.4 A
Degree of ProtectionHousing IP20; main circuit terminals IP10
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Mounting Position1 ... 6
Mounting on DIN RailTH35-15 and TH35-7.5, 35 mm mounting rail according to IEC 60715
Minimum Mounting DistanceElectrical Conductive Board, Vertical 75 mm
Short-Circuit Current Rating (SCCR)Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA
Published component typePower circuit-breaker for trafo/generator/installation protection
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Trip Class10
Actuator TypeLockable rotary handle, ON / OFF / TRIP indication

Catalogusinformatie kan fouten bevatten of verouderd zijn. Volledige specificaties en gecontroleerde gegevens zijn op aanvraag beschikbaar. Bevestig vóór bestelling het onderdeelnummer en de geschiktheid voor uw machine met ons.