Technische illustratie — ABB 1SAM350000R1012 — 1SAM350000R1012 — Motor protection circuit-breaker

Technische illustratie. Representative component image; exact configuration and appearance may vary. Afbeeldingen zijn uitsluitend ter referentie. Het geleverde onderdeel kan er anders uitzien.

ABB

1SAM350000R1012 — Motor protection circuit-breaker

Elektrotechniek en besturing

Onderdeelnummer: 1SAM350000R1012

ABB MS132-12 (1SAM350000R1012) is a three-pole manual motor starter and motor protection circuit-breaker with an adjustable 8–12 A overload setting. It provides manual switching and protection against overload, short circuit and phase failure. Rated operational power is 5.5 kW at 400 V three-phase under AC-3; the device has screw terminals and a lockable rotary handle.

Op zoek naar ABB 1SAM350000R1012? Deze catalogusreferentie is ingedeeld als ‘Elektrotechniek en besturing’. Stuur het onderdeelnummer en de gegevens van uw machine, zodat we de specificaties en beschikbaarheid kunnen controleren en een offerte inclusief verzending kunnen opstellen.

Beschikbaarheid op aanvraag

Prijs op aanvraag

Verzending inbegrepenGarantie en serviceOfferte voor dit onderdeel aanvragen

Technische specificaties

FabrikantABB
Onderdeelnummer1SAM350000R1012
CategorieElektrotechniek en besturing
Ex Operating InstructionsATEX - Operating instructions for Manual Motor Starters MS132 for potentially explosive areas
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter MS132-12.0
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS132
Product Net Width45 mm
Product Net Height97.8 mm
Product Net Depth / Length86.55 mm
Product Net Weight0.31 kg
Rated Service Short-Circuit Breaking Capacity (I cs )(230 V AC) 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (I cu )(230 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (I i )180 A
Setting Range8.0 ... 12 A
Rated Operational Power AC-3 (P e )(400 V) Three Phase 5.5 kW
Rated Operational Power AC-3e (P e )(400 V) Three Phase 5.5 kW
Rated Operational VoltageMain Circuit 690 V AC
Rated Operational Current (I e )12 A
Rated Operational Current AC-3 (I e )12 A
Rated Operational Current AC-3e (I e )12 A
Rated Operational Current DC-5 (I e )12 A
Rated Frequency (f)Main circuit: 50/60 Hz
Operating Frequency (f sw )0 ... 400 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 1.0 ... 2.3 W
Number of Poles3P
Conventional Free-air Thermal Current (I th )Main Circuit 12 A
Degree of ProtectionHousing IP20
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 6 mm²
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Trip class10
Rated service short-circuit breaking capacity at 400 V AC100 kA
Mounting on DIN railTH35-7.5 or TH35-15, 35 mm rail
Contact position indicationON / OFF / TRIP
Main circuit terminal protectionIP10

Catalogusinformatie kan fouten bevatten of verouderd zijn. Volledige specificaties en gecontroleerde gegevens zijn op aanvraag beschikbaar. Bevestig vóór bestelling het onderdeelnummer en de geschiktheid voor uw machine met ons.

Productvragen

Onderzoeksinformatie over dit onderdeel is nog niet beschikbaar in het Nederlands. Vraag ons team om hulp.

Offerte voor dit onderdeel aanvragen

Voel u thuis.

Kies uw taal en afleverbestemming. De definitieve prijs en verzending worden in uw offerte bevestigd.