Technische illustratie. Representative component image; exact configuration and appearance may vary. Afbeeldingen zijn uitsluitend ter referentie. Het geleverde onderdeel kan er anders uitzien.
1SAM360000R1009 — Motor protection circuit-breaker
relaisOnderdeelnummer: 1SAM360000R1009
ABB 1SAM360000R1009, type MO132-6.3, is a three-pole magnetic-only manual motor starter rated at 6.3 A. It provides manual switching and short-circuit protection; motor overload protection requires an appropriate thermal or electronic overload relay. The device has screw terminals and a rotary handle.
Op zoek naar ABB 1SAM360000R1009? Deze catalogusreferentie is ingedeeld als ‘relais’. Stuur het onderdeelnummer en de gegevens van uw machine, zodat we de specificaties en beschikbaarheid kunnen controleren en een offerte inclusief verzending kunnen opstellen.
Beschikbaarheid op aanvraag
Technische specificaties
| Fabrikant | ABB |
|---|---|
| Onderdeelnummer | 1SAM360000R1009 |
| Categorie | Elektrotechniek en besturing |
| Time-Current Characteristic Curve | Tripping characteristic - Manual Motor Starter Magnetic Only MO132-4 ... MO132-32 |
| Cut-off Current Characteristic | Cut-off Current Characteristic @ 400V -Manual Motor Starter MS132 |
| Product Net Width | 45 mm |
| Product Net Height | 90 mm |
| Product Net Depth / Length | 86.75 mm |
| Product Net Weight | 0.265 kg |
| Rated Service Short-Circuit Breaking Capacity (I cs ) | (230 V AC) 100 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (I cu ) | (230 V AC) 100 kA |
| Rated Instantaneous Short-Circuit Current Setting (I i ) | 78.8 A |
| Rated Operational Power AC-3 (P e ) | (400 V) Three Phase 2.2 kW |
| Rated Operational Power AC-3e (P e ) | (400 V) Three Phase 2.2 kW |
| Rated Operational Voltage | Main Circuit 690 V AC |
| Rated Operational Current (I e ) | 6.3 A |
| Rated Operational Current AC-3 (I e ) | 6.3 A |
| Rated Operational Current AC-3e (I e ) | 6.3 A |
| Rated Frequency (f) | Main circuit: 50 / 60 Hz |
| Operating Frequency (f sw ) | 0 ... 400 Hz |
| Rated Impulse Withstand Voltage (U imp ) | Main Circuit 6 kV |
| Rated Insulation Voltage (U i ) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 1.1 W |
| Number of Poles | 3P |
| Conventional Free-air Thermal Current (I th ) | Main Circuit 6.3 A |
| Degree of Protection | Housing IP20; main circuit terminals IP10 |
| Terminal Type | Screw Terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Tightening Torque | Main Circuit 0.8 ... 1.2 N·m |
| Wire Stripping Length | Main Circuit 9 mm |
| Mounting Position | 1 ... 6 |
| Published component type | Motor protection circuit-breaker |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
| Protection type | Magnetic only; separate overload protection required for motors |
| Setting Range | None |
| Mounting on DIN Rail | TH35-15 or TH35-7.5, 35 mm rail |
| Actuator Type | Rotary handle; ON / OFF / TRIP indication |
Catalogusinformatie kan fouten bevatten of verouderd zijn. Volledige specificaties en gecontroleerde gegevens zijn op aanvraag beschikbaar. Bevestig vóór bestelling het onderdeelnummer en de geschiktheid voor uw machine met ons.
Productvragen
Onderzoeksinformatie over dit onderdeel is nog niet beschikbaar in het Nederlands. Vraag ons team om hulp.
Offerte voor dit onderdeel aanvragen