Technische illustratie — ABB 1SAM360000R1010 — 1SAM360000R1010 — Motor protection circuit-breaker

Technische illustratie. Representative component image; exact configuration and appearance may vary. Afbeeldingen zijn uitsluitend ter referentie. Het geleverde onderdeel kan er anders uitzien.

ABB

1SAM360000R1010 — Motor protection circuit-breaker

relais

Onderdeelnummer: 1SAM360000R1010

ABB MO132-10 (1SAM360000R1010) is a three-pole, magnetic-only manual motor starter rated at 10 A. It provides manual switching and short-circuit protection with a disconnect function. An appropriate separate thermal or electronic overload relay is required for motor overload protection.

Op zoek naar ABB 1SAM360000R1010? Deze catalogusreferentie is ingedeeld als ‘relais’. Stuur het onderdeelnummer en de gegevens van uw machine, zodat we de specificaties en beschikbaarheid kunnen controleren en een offerte inclusief verzending kunnen opstellen.

Beschikbaarheid op aanvraag

Prijs op aanvraag

Verzending inbegrepenGarantie en serviceOfferte voor dit onderdeel aanvragen

Technische specificaties

FabrikantABB
Onderdeelnummer1SAM360000R1010
CategorieElektrotechniek en besturing
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter Magnetic Only MO132-4 ... MO132-32
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS132
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length86.75 mm
Product Net Weight0.265 kg
Rated Service Short-Circuit Breaking Capacity (I cs )(230 V AC) 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (I cu )(230 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (I i )125 A
Rated Operational Power AC-3 (P e )4 kW at 400 V, three-phase
Rated Operational Power AC-3e (P e )(400 V) Three Phase 4 kW
Rated Operational VoltageMain circuit: 690 V AC
Rated Operational Current (I e )10 A
Rated Operational Current AC-3 (I e )10 A
Rated Operational Current AC-3e (I e )10 A
Rated Frequency (f)Main circuit: 50/60 Hz
Operating Frequency (f sw )0 ... 400 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 2.2 W
Number of Poles3P
Conventional Free-air Thermal Current (I th )Main Circuit 10 A
Degree of ProtectionHousing IP20; main circuit terminals IP10
Terminal TypeScrew terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Mounting Position1 ... 6
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Mounting on DIN RailTH35-7.5 or TH35-15, 35 mm rail
Overload protectionSeparate appropriate thermal or electronic overload relay required for motor overload protection
Protection typeMagnetic short-circuit protection

Catalogusinformatie kan fouten bevatten of verouderd zijn. Volledige specificaties en gecontroleerde gegevens zijn op aanvraag beschikbaar. Bevestig vóór bestelling het onderdeelnummer en de geschiktheid voor uw machine met ons.