Schneider Electric

LC1F185 — Contactor

contactor

Onderdeelnummer: LC1F185

LC1F185 — Contactor — Schneider Electric reference LC1F185. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Op zoek naar Schneider Electric LC1F185? Deze catalogusreferentie is ingedeeld als ‘contactor’. Stuur het onderdeelnummer en de gegevens van uw machine, zodat we de specificaties en beschikbaarheid kunnen controleren en een offerte inclusief verzending kunnen opstellen.

Beschikbaarheid op aanvraag

Prijs op aanvraag

Verzending inbegrepenGarantie en serviceOfferte voor dit onderdeel aanvragen

Technische specificaties

FabrikantSchneider Electric
OnderdeelnummerLC1F185
CategorieElektrotechniek en besturing
RangeTeSys
product nameTeSys F
Product or Component TypeContactor
Poles description3P
power pole contact composition3 NO
[Ue] rated operational voltage<= 690 V AC 50/60 Hz <= 460 V DC
[Ie] rated operational current275 A 104 °F (40 °C)) <= 440 V AC-1 185 A 131 °F (55 °C)) <= 440 V AC-3
Motor power kW100 kW at 415 V AC 50/60 Hz (AC-3) 100 kW at 440 V AC 50/60 Hz (AC-3) 110 kW at 500 V AC 50/60 Hz (AC-3) 90 kW at 380...400 V AC 50/60 Hz (AC-3) 55 kW at 220...240 V AC 50/60 Hz (AC-3) 110 kW at 660...690 V AC 50/60 Hz (AC-3) 33 kW at 400 V AC 50/60 Hz (AC-4)
[Uc] control circuit voltage24...575 V AC 40...400 Hz with LX9 coil 24...460 V DC with LX4 coil 100...250 V AC 50/60 Hz with LXE coil 100...380 V DC with LXE coil
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
[Ith] conventional free air thermal current275 A (at 104 °F (40 °C))
Irms rated making capacity1850 A conforming to IEC 60947-4-1
Rated breaking capacity1480 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current1500 A 104 °F (40 °C) - 10 s 920 A 104 °F (40 °C) - 30 s 740 A 104 °F (40 °C) - 1 min 500 A 104 °F (40 °C) - 3 min 400 A 104 °F (40 °C) - 10 min
Associated fuse rating200 A aM at <= 440 V 315 A gG at <= 440 V
Average impedance0.33 mOhm - Ith 275 A 50 Hz
[Ui] rated insulation voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole25 W AC-1 12 W AC-3
Control circuit voltage limitsOperational: 0.85...1.1 Uc AC 40...400 Hz with LX9 coil Drop-out: 0.2...0.55 Uc AC 40...400 Hz with LX9 coil Operational: 0.85...1.1 Uc DC with LX4 coil Drop-out: 0.15...0.2 Uc DC with LX4 coil Operational: 85...275 V AC 50/60 Hz with LXE coil Drop-out: 0...60 V AC 50/60 Hz with LXE coil Operational: 85...418 V DC with LXE coil Drop-out: 0...45 V DC with LXE coil
Operating time35 ms closing with LX9 coil 130 ms opening with LX9 coil 30...40 ms closing with LX4 coil 30...50 ms opening with LX4 coil 40...80 ms closing with LXE coil 6...54 ms opening with LXE coil
Mounting SupportPlate
Connections - terminalsPower circuit bar 2 25 x 3 mm Power circuit lugs-ring terminals 1 0.2 in² (150 mm²) Power circuit connector 1 0.2 in² (150 mm²) Power circuit bolted connection Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)solid without cable end Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) Control circuit screw clamp terminals 1.0 0.000
Tightening torquePower circuit 159.3 lbf.in (18 N.m) Control circuit 10.6 lbf.in (1.2 N.m) Control circuit 5.3 lbf.in (0.6 N.m)
Inrush power in VA950…1180 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX9 coil 737…902 VA (at 68 °F (20 °C))with LX4 coil 280…310 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil 270…320 VA (at 68 °F (20 °C))with LXE coil
Hold-in power consumption in VA8.9…10.9 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX9 coil 4.13…5.07 VA (at 68 °F (20 °C))with LX4 coil 4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil 2.5…4.0 VA (at 68 °F (20 °C))with LXE coil
Published component typeContactor
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Catalogusinformatie kan fouten bevatten of verouderd zijn. Volledige specificaties en gecontroleerde gegevens zijn op aanvraag beschikbaar. Bevestig vóór bestelling het onderdeelnummer en de geschiktheid voor uw machine met ons.

Productvragen

Onderzoeksinformatie over dit onderdeel is nog niet beschikbaar in het Nederlands. Vraag ons team om hulp.

Offerte voor dit onderdeel aanvragen

Voel u thuis.

Kies uw taal en afleverbestemming. De definitieve prijs en verzending worden in uw offerte bevestigd.