Referentiebeeld van component: Published product/series reference; confirm the exact configuration and supplied appearance.

Representatief beeld van het componenttype, geen foto van dit exacte merk of onderdeelnummer. Bevestig de specificatie; het geleverde onderdeel kan er anders uitzien.

Schneider Electric

LV429101 — This Micrologic 5.2 A (Ammeter) is a 4 poles 4d electronic trip unit used on Compact NSX 100/160/250 circuit breakers. This 40A rating electronic trip unit is an optimum choice…

Sensoren & automatisering

Onderdeelnummer: LV429101

LV429101 — This Micrologic 5.2 A (Ammeter) is a 4 poles 4d electronic trip unit used on Compact NSX 100/160/250 circuit breakers. This 40A rating electronic trip unit is an optimum choice… — Schneider Electric reference LV429101. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Op zoek naar Schneider Electric LV429101? Deze catalogusreferentie is ingedeeld als ‘Sensoren & automatisering’. Stuur het onderdeelnummer en de gegevens van uw machine, zodat we de specificaties en beschikbaarheid kunnen controleren en een offerte inclusief verzending kunnen opstellen.

Beschikbaarheid op aanvraag

Prijs op aanvraag

Verzending inbegrepenGarantie en serviceOfferte voor dit onderdeel aanvragen

Technische specificaties

FabrikantSchneider Electric
OnderdeelnummerLV429101
CategorieSensoren & automatisering
RangeComPact
Range of ProductComPact NSX100...250
Product or Component TypeTrip unit
Range CompatibilityComPact NSX100 ComPact NSX160 ComPact NSX250
Number of poles4P
Protected poles description3t + N/2 3t + OSN 3t 4t
Trip unit protection functionsLSI
Protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection
Trip unit rated current40 A 104 °F (40 °C)
[Ue] rated operational voltage690 V AC 50/60 Hz
Network Frequency50/60 Hz
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range18...40 A
Long-time protection delay adjustment type trAdjustable
[tr] long-time protection delay adjustment range15…400 s 1.5 x Ir 0.35…11 s 7.2 x Ir 0.5…16 s 6 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdAdjustable
[tsd] Short-time protection delay adjustment range0…0.4 s I²t=off 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type IiAdjustable
[Ii] instantaneous protection pick-up adjustment range1.5...15 x In
Earth-leakage protectionWithout
Neutral protection settings0.5 x Ir 3t + N/2) 1 x Ir 4t) 1.6 x Ir 3t + OSN) No protection 3t)
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Display TypeLCD display
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Catalogusinformatie kan fouten bevatten of verouderd zijn. Volledige specificaties en gecontroleerde gegevens zijn op aanvraag beschikbaar. Bevestig vóór bestelling het onderdeelnummer en de geschiktheid voor uw machine met ons.

Productvragen

Onderzoeksinformatie over dit onderdeel is nog niet beschikbaar in het Nederlands. Vraag ons team om hulp.

Offerte voor dit onderdeel aanvragen

Voel u thuis.

Kies uw taal en afleverbestemming. De definitieve prijs en verzending worden in uw offerte bevestigd.