Rysunek techniczny — ABB 1SAM350000R1006 — 1SAM350000R1006 — Motor protection circuit-breaker

Rysunek techniczny. Representative component image; exact configuration and appearance may vary. Zdjęcia mają charakter poglądowy. Wygląd dostarczonej części może się różnić.

ABB

1SAM350000R1006 — Motor protection circuit-breaker

Elektryka i sterowanie

Numer części: 1SAM350000R1006

ABB MS132-1.6 (1SAM350000R1006) is a three-pole manual motor starter and motor protection circuit-breaker with an adjustable 1.0–1.6 A overload setting. It provides overload and short-circuit protection and phase-failure sensitivity, with a trip class 10 overload release. The screw-terminal device has a rotary ON/OFF/TRIP handle and is rated 0.55 kW for three-phase AC-3 operation at 400 V.

Szukasz części ABB 1SAM350000R1006? Ta pozycja katalogowa jest sklasyfikowana jako „Elektryka i sterowanie”. Prześlij numer części i dane maszyny, abyśmy mogli sprawdzić parametry i dostępność oraz przygotować ofertę z dostawą w cenie.

Dostępność na zapytanie

Cena na zapytanie

Wysyłka w cenieGwarancja i serwisUzyskaj wycenę tej części

Specyfikacja techniczna

ProducentABB
Numer części1SAM350000R1006
KategoriaElektryka i sterowanie
Ex Operating InstructionsATEX - Operating instructions for Manual Motor Starters MS132 for potentially explosive areas
Time-Current Characteristic CurveTripping characteristic - Manual Motor Starter MS132-1.6 valid for production date from week 34/2014
Cut-off Current CharacteristicCut-off Current Characteristic @ 400V -Manual Motor Starter MS132
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length86.75 mm
Product Net Weight0.265 kg
Rated Service Short-Circuit Breaking Capacity (I cs )100 kA at 230 V AC and 400 V AC
Rated Ultimate Short-Circuit Breaking Capacity (I cu )100 kA at 230 V AC and 400 V AC
Rated Instantaneous Short-Circuit Current Setting (I i )20 A
Setting Range1.0–1.6 A
Rated Operational Power AC-3 (P e )(400 V) Three Phase 0.55 kW
Rated Operational Power AC-3e (P e )(400 V) Three Phase 0.55 kW
Rated Operational VoltageMain circuit: 690 V AC; 250 V DC
Rated Operational Current (I e )1.6 A
Rated Operational Current AC-3 (I e )1.6 A
Rated Operational Current AC-3e (I e )1.6 A
Rated Operational Current DC-5 (I e )1.6 A
Rated Frequency (f)Main circuit: 50/60 Hz
Operating Frequency (f sw )0 ... 400 Hz
Rated Impulse Withstand Voltage (U imp )Main Circuit 6 kV
Rated Insulation Voltage (U i )690 V
Power Lossat Rated Operating Conditions per Pole 0.6 ... 1.7 W
Number of Poles3P
Conventional Free-air Thermal Current (I th )Main Circuit 1.6 A
Degree of ProtectionHousing IP20; main circuit terminals IP10
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Published component typeMotor protection circuit-breaker
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request
Overload Trip Class10
Mounting on DIN RailTH35-7.5 or TH35-15, according to IEC 60715
Actuator TypeRotary handle; ON/OFF/TRIP indication

Informacje katalogowe mogą zawierać błędy lub być nieaktualne. Pełne specyfikacje i zweryfikowane dane są dostępne na życzenie. Przed zamówieniem potwierdź z nami numer części i jej dopasowanie do maszyny.

Pytania o produkt

Wyniki badań dotyczących tej części nie są jeszcze dostępne po polsku. Skontaktuj się z naszym zespołem.

Uzyskaj wycenę tej części

Poczuj się jak u siebie.

Wybierz język i miejsce dostawy. Ostateczna cena i warunki wysyłki zostaną potwierdzone w wycenie.