C1632D160Nie udostępniono zdjęcia produktu

Pozycja katalogowa. Dostępność, dokładne parametry oraz dostawa oryginału lub zamiennika są potwierdzane w ofercie.

Schneider Electric

C1632D160 — This MicroLogic 2.2 is a 3 poles 3d electronic trip unit used on ComPacT NSX 160/250 circuit breakers. This 160A rating electronic trip unit is an optimum choice for all…

Czujniki i automatyka

Numer części: C1632D160

C1632D160 — This MicroLogic 2.2 is a 3 poles 3d electronic trip unit used on ComPacT NSX 160/250 circuit breakers. This 160A rating electronic trip unit is an optimum choice for all… — Schneider Electric reference C1632D160. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Szukasz części Schneider Electric C1632D160? Ta pozycja katalogowa jest sklasyfikowana jako „Czujniki i automatyka”. Prześlij numer części i dane maszyny, abyśmy mogli sprawdzić parametry i dostępność oraz przygotować ofertę z dostawą w cenie.

Dostępność na zapytanie

Cena na zapytanie

Wysyłka w cenieGwarancja i serwisUzyskaj wycenę tej części

Specyfikacja techniczna

ProducentSchneider Electric
Numer częściC1632D160
KategoriaCzujniki i automatyka
RangeComPacT
Range of productComPacT NSX100...250
Product or component typeTrip unit
Range compatibilityComPacT NSX160 ComPacT NSX250
Poles description3P
Protected poles description3D
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rating160 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range63...160 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5...10 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range2400 A
Earth-leakage protectionWithout
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Informacje katalogowe mogą zawierać błędy lub być nieaktualne. Pełne specyfikacje i zweryfikowane dane są dostępne na życzenie. Przed zamówieniem potwierdź z nami numer części i jej dopasowanie do maszyny.