Pozycja katalogowa. Dostępność, dokładne parametry oraz dostawa oryginału lub zamiennika są potwierdzane w ofercie.
C4031M320 — This MicroLogic 1.3 M is a 3 poles 3d electronic trip unit used on ComPacT NSX 400/630 circuit breakers. This 320A rating electronic trip unit is an optimum choice for motor…
Czujniki i automatykaNumer części: C4031M320
C4031M320 — This MicroLogic 1.3 M is a 3 poles 3d electronic trip unit used on ComPacT NSX 400/630 circuit breakers. This 320A rating electronic trip unit is an optimum choice for motor… — Schneider Electric reference C4031M320. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.
Szukasz części Schneider Electric C4031M320? Ta pozycja katalogowa jest sklasyfikowana jako „Czujniki i automatyka”. Prześlij numer części i dane maszyny, abyśmy mogli sprawdzić parametry i dostępność oraz przygotować ofertę z dostawą w cenie.
Dostępność na zapytanie
Specyfikacja techniczna
| Producent | Schneider Electric |
|---|---|
| Numer części | C4031M320 |
| Kategoria | Czujniki i automatyka |
| Range | ComPacT |
| Range of product | ComPacT NSX400...630 |
| Product or component type | Trip unit |
| Range compatibility | ComPacT NSX400 ComPacT NSX630 |
| Poles description | 3P |
| Protected poles description | 3D |
| Trip unit protection functions | SI |
| Protection type | S : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
| Trip unit rating | 320 A at 65 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network frequency | 50/60 Hz |
| Circuit breaker mounting mode | Fixed |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1600 A 1920 A 2240 A 2560 A 2880 A 3200 A 3520 A 3840 A 4160 A |
| Short-time protection delay adjustment type tsd | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 4800 A |
| Earth-leakage protection | Without |
| Local signalling | Flashing LED (green) for ready to operate |
| Reference status | Published part reference; specification and fitment require confirmation |
| Availability | On request |
Informacje katalogowe mogą zawierać błędy lub być nieaktualne. Pełne specyfikacje i zweryfikowane dane są dostępne na życzenie. Przed zamówieniem potwierdź z nami numer części i jej dopasowanie do maszyny.
Pytania o produkt
Wyniki badań dotyczących tej części nie są jeszcze dostępne po polsku. Skontaktuj się z naszym zespołem.
Uzyskaj wycenę tej części