C4032M320Nie udostępniono zdjęcia produktu

Pozycja katalogowa. Dostępność, dokładne parametry oraz dostawa oryginału lub zamiennika są potwierdzane w ofercie.

Schneider Electric

C4032M320 — This MicroLogic 2.3 M is a 3 poles 3d electronic trip unit used on ComPacT NSX 400/630 circuit breakers. This 320A rating magnetic trip unit is an optimum choice for motor…

Czujniki i automatyka

Numer części: C4032M320

C4032M320 — This MicroLogic 2.3 M is a 3 poles 3d electronic trip unit used on ComPacT NSX 400/630 circuit breakers. This 320A rating magnetic trip unit is an optimum choice for motor… — Schneider Electric reference C4032M320. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Szukasz części Schneider Electric C4032M320? Ta pozycja katalogowa jest sklasyfikowana jako „Czujniki i automatyka”. Prześlij numer części i dane maszyny, abyśmy mogli sprawdzić parametry i dostępność oraz przygotować ofertę z dostawą w cenie.

Dostępność na zapytanie

Cena na zapytanie

Wysyłka w cenieGwarancja i serwisUzyskaj wycenę tej części

Specyfikacja techniczna

ProducentSchneider Electric
Numer częściC4032M320
KategoriaCzujniki i automatyka
RangeComPacT
Range of productComPacT NSX400...630
Product or component typeTrip unit
Range compatibilityComPacT NSX400 ComPacT NSX630
Poles description3P
Protected poles description3D
Trip unit protection functionsLSoI
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Trip unit rating320 A at 65 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Complementary motor protectionPhase unbalance
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range160...320 A
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range5...13 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range4800 A
Earth-leakage protectionWithout
Local signallingFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Informacje katalogowe mogą zawierać błędy lub być nieaktualne. Pełne specyfikacje i zweryfikowane dane są dostępne na życzenie. Przed zamówieniem potwierdź z nami numer części i jej dopasowanie do maszyny.

Pytania o produkt

Wyniki badań dotyczących tej części nie są jeszcze dostępne po polsku. Skontaktuj się z naszym zespołem.

Uzyskaj wycenę tej części

Poczuj się jak u siebie.

Wybierz język i miejsce dostawy. Ostateczna cena i warunki wysyłki zostaną potwierdzone w wycenie.