Zdjęcie poglądowe typu części: Published product/series reference; confirm the exact configuration and supplied appearance.

Poglądowe zdjęcie typu części, nie fotografia tej dokładnej marki ani numeru katalogowego. Potwierdź parametry; dostarczona część może wyglądać inaczej.

Schneider Electric

LV430093 — This TM100G is a 4 poles 4d thermal-magnetic trip unit used on Compact NSX 100/160/250 circuit breakers. This 100A rating thermal-magnetic trip unit is an optimum choice for…

Elektryka i sterowanie

Numer części: LV430093

LV430093 — This TM100G is a 4 poles 4d thermal-magnetic trip unit used on Compact NSX 100/160/250 circuit breakers. This 100A rating thermal-magnetic trip unit is an optimum choice for… — Schneider Electric reference LV430093. Request a quotation including shipping to your destination. Send equipment details and certificate requirements so we can confirm the exact specification, fitment, availability and warranty terms before ordering.

Szukasz części Schneider Electric LV430093? Ta pozycja katalogowa jest sklasyfikowana jako „Elektryka i sterowanie”. Prześlij numer części i dane maszyny, abyśmy mogli sprawdzić parametry i dostępność oraz przygotować ofertę z dostawą w cenie.

Dostępność na zapytanie

Cena na zapytanie

Wysyłka w cenieGwarancja i serwisUzyskaj wycenę tej części

Specyfikacja techniczna

ProducentSchneider Electric
Numer częściLV430093
KategoriaElektryka i sterowanie
RangeComPact
Range of productComPact NSX100...250 ComPact NSX100...250 DC
Product or component typeTrip unit
Range compatibilityComPact NSX100 ComPact NSX160 ComPact NSX100 DC
Number of poles4P
Protected poles description4t
Trip unit protection functionsLI
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rated current100 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz 750 V DC
Network frequency50/60 Hz
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120…400 s at 1.5 x In
Short-time protection pick-up adjustment type IsdFixed
[Isd] Short-time protection pick-up adjustment range320 A
Short-time protection delay adjustment type tsdFixed
Earth-leakage protectionWithout
Neutral protection settings1 x Ir (4t)
Reference statusPublished part reference; specification and fitment require confirmation
AvailabilityOn request

Informacje katalogowe mogą zawierać błędy lub być nieaktualne. Pełne specyfikacje i zweryfikowane dane są dostępne na życzenie. Przed zamówieniem potwierdź z nami numer części i jej dopasowanie do maszyny.

Pytania o produkt

Wyniki badań dotyczących tej części nie są jeszcze dostępne po polsku. Skontaktuj się z naszym zespołem.

Uzyskaj wycenę tej części

Poczuj się jak u siebie.

Wybierz język i miejsce dostawy. Ostateczna cena i warunki wysyłki zostaną potwierdzone w wycenie.